Application Example #2 Appendix A: MS-5210UD
ACM-8RF PN 50362:C 03/21/01
25
Application Example #2
Zone Alarm and Trouble Activation (no system status relays)
Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).
For this example, two relays per zone are required for alarm and trouble,
therefore, three ACM-8RFs are necessary. In this example, the ACM-8RFs are
the only devices on the EIA-485 bus. Set the ACM-8RF address switches so
that SW1 = 0 and SW2 = 1 on each
of the three ACM-8RFs. Enter this address
into the MS-5210UD Level 3 addresses 02 - 03. Refer to the following chart
for switch settings:
Table 7 Settings for Zone Alarm and Trouble Activation
MS-5210UD
Zone
ACM-8RF
Alarm Relay
ACM-8RF
Trouble Relay
Switch Settings
Z1 Relay 1 Relay 5 1st ACM-8RF
SW1=0; SW2=1 (Address ‘01’)
SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=ON
Z2 Relay 2 Relay 6
Z3 Relay 3 Relay 7
Z4 Relay 4 Relay 8
Z5 Relay 1 Relay 5 2nd ACM-8RF
SW1=0; SW2=1 (Address ‘01’)
SW3-4 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=ON
Z6 Relay 2 Relay 6
Z7 Relay 3 Relay 7
Z8 Relay 4 Relay 8
Z9 Relay 1 Relay 5 3rd ACM-8RF
SW1=0; SW2=1 (Address ‘01’)
SW3-1 = ON; SW3-6 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=OFF
Z10 Relay 2 Relay 6
n/a Relay 3 Relay 7
n/a Relay 4 Relay 8