G Control Relay ModuleACM-8RFInstruction ManualDocument 5036203/21/2001 Rev:CPN 50362:C0 ECN 01-155
1. Introduction Related Documentation10ACM-8RF PN 50362:C 03/21/01NOTES
ACM-8RF PN 50362:C 03/21/01112. InstallationMounting the Enclosure.Select and remove the appropriate knockout(s) on the ABS-8RF enclosure.Securely m
2. Installation Wiring the Relay Terminal Blocks12ACM-8RF PN 50362:C 03/21/01Wiring the Relay Terminal BlocksThe ACM-8RF provides eight relays with
Wiring the EIA-485 Terminal Blocks 2. InstallationACM-8RF PN 50362:C 03/21/0113Wiring the EIA-485 Terminal BlocksCommunications between the Fire Ala
2. Installation Wiring the EIA-485 Terminal Blocks14ACM-8RF PN 50362:C 03/21/01EIA-485 Shield Not in ConduitWhen the EIA-485 wiring is not in condui
Configuring the ACM-8RF 2. InstallationACM-8RF PN 50362:C 03/21/0115Configuring the ACM-8RFAddress Switches - SW1 and SW2It is critical to the opera
2. Installation Mounting in the ABS-8RF Enclosure16ACM-8RF PN 50362:C 03/21/01Mode Select Switch - SW4Set the mode of operation as follows: Figure 1
UL Power-limited Wiring Requirements 2. InstallationACM-8RF PN 50362:C 03/21/0117UL Power-limited Wiring RequirementsPower-limited and nonpower-limi
2. Installation UL Power-limited Wiring Requirements18ACM-8RF PN 50362:C 03/21/01NOTES
ACM-8RF PN 50362:C 03/21/01193. Electrical Ratings24 VDCMust be power-limited.Current Draw from 24 VDC Input @ Normal Standby: 0.030 ampsMaximum cur
LimWarSm.p65 01/10/2000An automatic fire alarm system–typically made upof smoke detectors, heat detectors, manual pullstations, audible warning dev
3. Electrical Ratings Power Requirements20ACM-8RF PN 50362:C 03/21/01NOTES
ACM-8RF PN 50362:C 03/21/0121Appendix A: MS-5210UDCapabilitiesWhen installed with an MS-5210UD Fire Alarm Control Panel (FACP), the ACM-8RF Relay Co
Appendix A: MS-5210UD FACP Activations22ACM-8RF PN 50362:C 03/21/01FACP ActivationsDIP switch SW3 on the ACM-8RF Relay Control Module is used to det
FACP Activations Appendix A: MS-5210UDACM-8RF PN 50362:C 03/21/0123Alarm and Trouble ActivationTable 5 provides the switch settings for ACM-8RF DIP
Appendix A: MS-5210UD Application Example #124ACM-8RF PN 50362:C 03/21/01Application Example #1Zone Alarm Only Activation (no system status relays)P
Application Example #2 Appendix A: MS-5210UDACM-8RF PN 50362:C 03/21/0125Application Example #2Zone Alarm and Trouble Activation (no system status r
Appendix A: MS-5210UD Application Example #326ACM-8RF PN 50362:C 03/21/01Application Example #3Two LED-10 Annunciators and 10 Alarm Only Relays(no s
Application Example #3 Appendix A: MS-5210UDACM-8RF PN 50362:C 03/21/0127The figure below is provided as an application example of using two LED-10s
Appendix A: MS-5210UD Application Example #428ACM-8RF PN 50362:C 03/21/01Application Example #4Two LED-10 Annunciators, 10 Alarm Only Relays and 20
Application Example #4 Appendix A: MS-5210UDACM-8RF PN 50362:C 03/21/0129Since each ACM-8RF module contains eight relays, two ACM-8RF modules are re
LimWarSm.p65 01/10/2000WARNING - Several different sources of power canbe connected to the fire alarm control panel.Disconnect all sources of power
Appendix A: MS-5210UD Application Example #430ACM-8RF PN 50362:C 03/21/01The figure below is provided as an application example of using two LED-10s
ACM-8RF PN 50362:C 03/21/0131Appendix B: MS-9200CapabilitiesWhen installed with an MS-9200 Fire Alarm Control Panel (FACP), the ACM-8RF Relay Contro
Appendix B: MS-9200 FACP Activations32ACM-8RF PN 50362:C 03/21/01FACP ActivationsDIP switch SW3 on the ACM-8RF Relay Control Module is used to deter
FACP Activations Appendix B: MS-9200ACM-8RF PN 50362:C 03/21/0133Alarm and Trouble ActivationTable 11 provides the switch settings for ACM-8RF DIP s
Appendix B: MS-9200 FACP Activations34ACM-8RF PN 50362:C 03/21/01Z21 Relay 1 Relay 58th ACM-8RFSW3-4 = ON;SW3-6 = ONAll other SW3s = OFFZ22 Relay 2
FACP Activations Appendix B: MS-9200ACM-8RF PN 50362:C 03/21/0135Status functions of first 16 relays if the FACP has a UDACT-F installed. Table 12
Appendix B: MS-9200 FACP Activations36ACM-8RF PN 50362:C 03/21/01NOTES
ACM-8RF PN 50362:C 03/21/0137Appendix C: MS-9600CapabilitiesWhen installed with an MS-9600 Fire Alarm Control Panel (FACP), the ACM-8RF Relay Contro
Appendix C: MS-9600 Configuration38ACM-8RF PN 50362:C 03/21/01ConfigurationSetting Rotary SwitchesThe Address Select Rotary Switches (SW1 & SW2)
Configuration Appendix C: MS-9600ACM-8RF PN 50362:C 03/21/0139Mode SelectAlarm Only or Alarm/Trouble ModeDetermine if “alarm only” mode or “alarm/t
4ACM-8RF PN 50362:C 03/21/01This page intentionally left blank
Appendix C: MS-9600 Configuration40ACM-8RF PN 50362:C 03/21/01Setting the DIP SwitchesThe DIP switch (SW3), in combination with the Rotary Switches,
Configuration Appendix C: MS-9600ACM-8RF PN 50362:C 03/21/0141Alarm and Trouble ActivationWhen “Alarm/Trouble” is selected, relays 1 - 4 respond to
Appendix C: MS-9600 Configuration42ACM-8RF PN 50362:C 03/21/01The following table displays an example of how to set the DIP switches on four (4) ACM
IndexACM-8RF PN 50362:C 03/21/0143IndexNumerics120 ohm ELR 14, 21, 31, 37120 volts AC 1324 VDC 8, 11, 19AABS-8RF 7, 11, 16AC Fail 21, 31, 37activati
Index44ACM-8RF PN 50362:C 03/21/01multiple modules 11multiple shields 13multiple wiring 14NNAC Fault 21, 31, 37NEC Article 250 11no conduit 14nonpow
ACM-8RF PN 50362:C 03/21/0145
46ACM-8RF PN 50362:C 03/21/01
LimWarSm.p65 01/10/2000The manufacturer warrants its products to be free from defects in materials andworkmanship for eighteen (18) months from the
World HeadquartersOne Fire-Lite Place, Northford, CT 06472-1653 USA203-484-7161 • Fax 203-484-7118www.firelite.com
Table of ContentsTable of Contents1. IntroductionGeneral...
Table of ContentsAppendix B: MS-9200Capabilities ...31Testing..
ACM-8RF PN 50362:C 03/21/0171. IntroductionGeneralThe ACM-8RF Relay Control Module contains eight high current (5 amps) Form-C relays. The module i
1. Introduction Features8ACM-8RF PN 50362:C 03/21/01FeaturesFigure 1 ACM-8RF FeaturesRelaysThe Relay Control Module provides eight Form-C relays wi
Related Documentation 1. IntroductionACM-8RF PN 50362:C 03/21/019EIA-485 CommunicationsWiring to removable terminal block TB2 is for communications